Range of product | Easergy T300 |
---|---|
Device short name | HU250 |
Product or component type | Communication gateway |
---|---|
Communication port protocol | DNP3 serial and TCP master/slave Modbus serial and TCP master/slave IEC 61850-8-1 master/slave IEC 60870-5-104 master/slave IEC 60870-5-101 slave |
Communication port support | ETHERNET 4 RJ45 RS232/485 Modbus/ASCII 1 RJ45 RS485/RS232 1 RJ45 3G/4G 1 SMA |
Data recording | Event logs 4 data logs 1 ms time stamps 500000 events Sequence of event recording |
Memory capacity | 16 MB |
Time synchronisation protocol | NTP SNTP GPS |
Synchronisation time between inputs | 1 ms |
Control type | Illuminated push-button status: |
Communication service | Web server local WiFi: Web server local Ethernet: Web server remote WAN: |
web services | Event log Alarm Operating/Status report Assistance in commissioning and operating the installation Security/authority verification Reports and diagrams |
Programming language | Calculation formula ST (structured text) IL (instruction list) LD (ladder) FBD (function block diagram) SFC (sequential function chart) |
Number of inputs | 6 digital multi-purpose conforming to IEC 61131-2 type 3 2 digital remote control 2 analog measure temperature |
Number of outputs | 2 digital (relay) multi-purpose: |
[Us] rated supply voltage | 12…48 V DC +/- 20 % |
power consumption in VA | 3 VA |
language | Multi-language |
---|---|
Electromagnetic compatibility | Electrical fast transient/burst immunity test – test level: level 4 criteria A conforming to IEC 61000-4-4 Conducted RF disturbances – test level: level 3 criteria A conforming to IEC 61000-4-6 Conducted disturbance emission – test level: level 4 criteria A conforming to IEC 61000-4-16 100 kHz damped oscillating wave – test level: level 3 criteria A conforming to IEC 61000-4-12 Radiated radio-frequency electromagnetic field immunity test – test level: level 4 criteria A conforming to IEC 61000-4-3 Immunity to voltage dips criteria A conforming to IEC 61000-4-29 Electrostatic discharge – test level: level 4 criteria B conforming to IEC 61000-4-2 Surge immunity test – test level: level 3 criteria A conforming to IEC 61000-4-5 Magnetic field at power frequency – test level: level 5 criteria B conforming to IEC 61000-4-8 Conducted and radiated emissions class A conforming to EN 55022 |
Fixing mode | Clip-in (DIN rail) |
Type of installation | Indoor Outdoor in cabinet |
IP degree of protection | IP2X body: conforming to IEC 60529 IP4X front: conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Relative humidity | 5…95 % conforming to IEC 60068-2-30 |
Mechanical robustness | Vibrations 10…2000 Hz 1 gn 10 cycles conforming to IEC 60068-2-6 Bumps 10 gn 16 ms 1000 bumps non energized conforming to IEC 60068-2-29 Shocks 11 ms 3 pulses in operation conforming to IEC 60068-2-27 |
Ambient air temperature for storage | -40…85 °C |
Ambient air temperature for operation | -40…70 °C |
Operating altitude | 3000 m |
Product certifications | CE |
Standards | IEC 60255-27 |
Height | 140 mm |
Width | 90 mm |
Depth | 140 mm |
Net weight | 0.55 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 11.900 cm |
Package 1 Width | 19.100 cm |
Package 1 Length | 19.800 cm |
Package 1 Weight | 765.000 g |
Unit Type of Package 2 | S04 |
Number of Units in Package 2 | 9 |
Package 2 Height | 30.000 cm |
Package 2 Width | 40.000 cm |
Package 2 Length | 60.000 cm |
Package 2 Weight | 7.277 kg |